Tower Model (With LCD Display) |
VGD-700 |
VGD-1000 |
VGD-1500 |
19 Rack-Mount Model |
VGD-700 -RM |
VGD-1000-RM |
VGD-1500-RM |
INPUT |
Capacity (VA) |
700VA |
1000VA |
1500VA |
Capacity (W) |
490W |
700W |
1050W |
Voltage |
100V/110V/115V/120V/127V |
208V/220V/230V/240V |
Voltage/Range |
Load Capacity |
Voltage/Range |
Load Capacity |
60 ~ 69V |
0 ~ 40% |
120 ~ 139V |
0 ~ 40% |
70 ~ 79V |
0 ~ 70% |
140 ~ 159V |
0 ~ 70% |
80 ~ 144V |
0 ~ 100% |
160 ~ 276V |
0 ~ 100% |
|
Frequency |
50 / 60 Hz Auto Sensing |
OUTPUT |
Voltage (on battery) |
100V, 110V, 115V, 120V, 127V or 208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage) |
Frequency (on battery) |
50 / 60 Hz +/-0.5% |
Transfer Time |
0 ms |
Overload Recovery |
Auto transfer to UPS |
High Efficiency Mode (AC to AC) |
> 95 % |
Line Mode |
> 86% |
UPS Green Mode |
Energy saving function (No Load Shutdown) |
UPS Design Technology |
On-Line / Fully digitized microprocessor controlled |
Output Wave Form |
Sinewave |
Harmonic Distortion |
< 3% of T.H.D. at linear load |
Crest Factor |
3 : 1 |
PROTECTION & FILTERING |
Surge Protection |
120V (IEEE C62.41) / 230V (IEEEC61000-4-5 level 3) |
Overload Protection |
125% for 1 minute and 150% for 10 seconds |
Short Circuit |
UPS output cut off immediately or input fuse / circuit breaker protection |
SYSTEM
DISPLAY / WARNING |
Visual Display (LED Model) |
UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red) |
Visual Display (LCD Model) |
Input / output voltage, input / output frequency, on-line mode, back up mode, battery capacity, load level |
Audible Alarm (Battery Back-Up) |
Beep every 5 sec |
UPS Fault |
Continuous beeping sound and LCD display |
Communication |
RS-232 Serial Port and USB |
BATTERY |
Type |
Sealed, maintenance-free lead acid batteries |
DC Voltage (V) Battery (Tower ) |
24V / 12V7.2AH x 2 |
36V / 12V7.2AH x 3 |
36V / 12V9AH x 3 |
DC Voltage (V) Battery (1U) |
24V / 6V7.2AH x 4 |
None |
DC Voltage (V) Battery (2U) |
24V / 12V7.2AH x 2 |
36V / 12V7.2AH x 3 |
36V / 12V9AH x 3 |
Typical Recharge Time to 90% Full |
3 hours |
Management |
Self-test, adjustable battery transfer points and alarm settings |
Battery Protection |
Cut off without draining any current when battery is low |
Cold Start (DC Start) |
YES |
Back Up Time (Tower Model) |
7 min |
Back Up Time
(Full Load) |
2U* = 7 min,
1U = 7 min |
2U* = 7 min,
1U = 4 min |
6 min |
Back Up Time
(Half Load) |
2U*= 15 min,
1U = 15 min |
2U*= 15 min,
1U = 10 min |
15 min |
PHYSICAL |
Input lnlet |
NEMA 5-15 (120V) / IEC 320 (230V) |
Receptacles |
NEMA 5-15 (120V) / IEC 320 (230V) |
Total Receptacles
(UPS+Surge / Surge Only)
|
6 (120V), 4 (230V) |
Tower Dimensions lnches
mm (inch) W x D x H |
152 x 420 x 237
(6.0 x 16.5 x 9.3) |
19 Rack-Mount Dimensions mm (inch)
|
428 x 525 x 44 (16.9 x 20.7 x 1.7) 1U |
None |
428 x 425 x 84 (16.9 x 16.7 x 3.3) 2U |
Net Weight kg (lb)
Tower model |
13.9 (30.6)
|
171. (37.6) |
17.7 (38.9) |
Shipping Weight kg (lb)
Tower Model |
15.6 (34.3) |
18.9 (41.6) |
19.5 (42.9) |
ENVIRONMENT |
Operating Temperature |
0 - 40 deg C / 32 ~ 104 deg F |
Storage Temperature |
-20 ~ 50 deg C / -4 ~ 122 deg F |
Altitude |
3,500 meters max |
Audible Noise
(1 meter from surface) |
< 40 dBA |
Relative Humidity |
0 ~ 95% humidity, non-condensing |
CONFORMANCE |
Safety |
UL 1778, CE |
EMC (EMS / EMI) |
IEC 61000-4, FCC Part 15, CISPR 22 |
Warranty policy |
Warranty policy may vary depends on region |