Tower Model (With LCD Display) |
VGD-4000 |
VGD-5000 |
19" Rack-Mount Model |
VGD-4000-RM |
VGD-5000-RM |
INPUT |
Capacity (VA) |
4000VA |
5000VA |
Capacity (W) |
2800W |
3500W |
Voltage |
208V/220V/230V/240V
|
Voltage/Range
|
Load Capacity
|
120 ~ 139V
|
0 ~ 40%
|
140 ~ 159V
|
0 ~ 70%
|
160 ~ 276V
|
0 ~ 100%
|
|
Frequency |
50 / 60 Hz Auto Sensing |
OUTPUT |
Voltage (on battery) |
100V, 110V, 115V, 120V, 127V or 208V,
220V, 230V, 240V +/-2% (Selectable Output Voltage) |
Frequency (on battery) |
50 / 60 Hz +/-0.5% |
Transfer Time |
0 ms |
Overload Recovery |
Auto transfer to UPS |
High Efficiency Mode (AC to AC) |
> 95 % |
Line Mode |
> 86% |
UPS Green Mode |
Energy saving function (No Load
Shutdown) |
UPS Design Technology |
On-Line / Fully digitized
microprocessor controlled |
Output Wave Form |
Sinewave |
Harmonic Distortion |
< 3% of T.H.D. at linear load |
Crest Factor |
3 : 1 |
PROTECTION & FILTERING |
Surge Protection |
120V (IEEE C62.41) / 230V
(IEEEC61000-4-5 level 3) |
Overload Protection |
125% for 1 minute and 150% for 10
seconds |
Short Circuit |
UPS output cut off immediately or
input fuse / circuit breaker protection |
SYSTEM
DISPLAY / WARNING |
Visual Display (LED Model) |
UPS on(green), line-mode(green),
battery mode(yellow), bypass(yellow), fault(red) |
Visual Display (LCD Model) |
Input / output voltage, input /
output frequency, on-line mode, back up mode, battery capacity, load
level |
Audible Alarm (Battery Back-Up) |
Beep every 5 sec |
UPS Fault |
Continuous beeping sound and LCD
display |
Communication |
RS-232 Serial Port and USB |
BATTERY |
Type |
Sealed, maintenance-free lead acid
batteries |
DC Voltage (V) Battery (Tower ) |
120V / 12V7.2AH x 10 |
120V / 12V9AH x 10 |
DC Voltage (V) Battery (1U) |
None |
DC Voltage (V) Battery (2U) |
120V / 12V7.2AH x 10 |
120V / 12V9AH x 10 |
Typical Recharge Time to 90% Full |
3 hours |
Management |
Self-test, adjustable battery
transfer points and alarm settings |
Battery Protection |
Cut off without draining any current
when battery is low |
Cold Start (DC Start) |
YES |
Back Up Time (Full Load) |
5 mins |
6 mins |
Back Up Time
(Half Load) |
15 mins |
15 mins |
PHYSICAL |
Input lnlet |
NEMA 5-15 (120V) / IEC 320 (230V) |
Receptacles |
NEMA 5-15 (120V) / IEC 320 (230V) |
Total Receptacles
(UPS+Surge / Surge Only)
¡@ |
IEC 320 C13 * 8
IEC 320 C19 * 2 |
Tower Dimensions lnches
mm (inch) W x D x H |
257 * 540 * 440 (mm)
406*682*525(mm) (Shipping Dimension)
¡@ |
Net Weight kg (lb)
Tower model |
86kg
¡@ |
Shipping Weight kg (lb)
Tower Model |
106kg |
19" Rack-Mount Dimensions mm (inch)
¡@ |
428 x 597 x 130 (16.9" x 23.5" x
5.1") 3U (Power Module)
428 x 597 x 130 (16.9" x 23.5" x 5.1") 3U (Batery Module) |
Net Weight kg (lb)
Rack Mount model |
20.0 (44.0) (Power Module) |
66.0 (145.2) (Battery Module) |
Shipping Weight kg (lb)
Rack mount Model |
24.0 (52.8) (Power Module) |
75.5 (166.1) (Battery Module) |
ENVIRONMENT |
Operating Temperature |
0 - 40 deg C / 32 ~ 104 deg F |
Storage Temperature |
-20 ~ 50 deg C / -4 ~ 122 deg F |
Altitude |
3,500 meters max |
Audible Noise
(1 meter from surface) |
< 40 dBA |
Relative Humidity |
0 ~ 95% humidity, non-condensing |
CONFORMANCE |
Safety |
UL 1778, CE |
EMC (EMS / EMI) |
IEC 61000-4, FCC Part 15, CISPR 22 |
Warranty policy |
Warranty policy may vary depends on
region |